UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Current
equalization
detection
EOD restart
EOD restart
delay(min)
Bypass Settings
Figure 5-28 Bypass Settings
Issue 06 (2023-08-25)
Description
Monitors the current
differences between racks or
modules. If this parameter is
set to Enable, the Mod. Cur.
Eql. Data can be viewed on
the running information
page.
The UPS transfers to battery
mode when the mains is
abnormal. When batteries
reach the end of discharge
(EOD) threshold and the
bypass is unavailable, the
UPS powers off. After the
mains recovers, the UPS will
automatically restart if EOD
restart is set to Enable.
If this parameter is set to
Disable, you need to
manually rectify the fault
and then start the UPS, or
you can set this parameter to
Enable.
If EOD restart is set to
Enable, the UPS starts
working after the time set for
EOD restart delay when the
input recovers from a power
failure upon battery EOD.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 LCD Interface
Default Value
Value Range
Disable
Disable,
Enable
Enable
Disable,
Enable
10
1–1440
143