UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 4-8 Installing an expansion bolt (unit: mm)
1.
2.
3.
4.
Step 3 Move the UPS over its castors to the installation position.
Step 4 If the castors need to hang in the air, perform
Installation.
Step 5 Open the front and rear doors of the cabinet.
Step 6 Insert four M12x115 expansion bolts into the expansion bolt holes in the floor, and
tighten the expansion bolts.
Issue 06 (2023-08-25)
Drill a hole into the concrete floor using a hammer drill. The hole depth
ranges from 52 mm to 60 mm.
Slightly tighten the expansion bolt and vertically insert it into the hole. Knock
the expansion bolt using a rubber mallet until the expansion sleeve is fully
inserted into the hole.
Partially tighten the expansion bolt.
Remove the bolt, spring washer, and flat washer.