Figure 4-9 Tightening expansion bolts
----End
Non-Secured Installation
Step 1 Raise the four anchor bolts at the bottom of the UPS cabinet by using a wrench
until all the four castors at the bottom hang in the air and the anchor bolts bear
all of the cabinet weight.
1. Wrench an anchor bolt clockwise to elevate the cabinet, or wrench it
2. To prevent cabinet tilting, adjust the four anchor bolts instead of one anchor
3. Use a measuring tape for measurement when leveling the cabinet to ensure
4. Do not remove anchor bolts. Otherwise, you need to rework them for use.
Step 2 Check the cabinet levelness using a level. If the cabinet is not level, wrench the
anchor bolts.
Issue 06 (2023-08-25)
NO TICE
counterclockwise to lower the cabinet. The anchor bolts can be wrenched
within a range of 0–8 mm.
bolt.
that the height between the cabinet top and the floor is 2000 mm (tolerance
+3 mm).