Huawei UPS5000-E User Manual page 49

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Silk Screen
Type
BCB_OL
DI
BCB_STA
DI
BCB_DRV
DO
BCB_0V
EPO_NO
DI
EPO_12V
EPO_NC
DI
EPO_12V
Issue 06 (2023-08-25)
Working
Signal
Principle
Description
Port for
detecting the
BCB box
Port for
monitoring the
BCB
Drives BCB
tripping. When
the voltage is
+12 V, the
circuit breaker
trips.
Port for signal
ground
Emergency
power-off
(EPO) port
+12V
EPO port
+12V
Copyright © Huawei Digital Power Technologies Co., Ltd.
Status Description
● Grounded: BCB
box connected
● Disconnected:
BCB box not
connected
● Closed: BCB On
● Open: BCB Off
● 0 V: not drive
BCB tripping
● 12 V: drive BCB
tripping
If the normally
open (NO) signal
port is connected
to the EPO_12V
port, EPO is
triggered.
If the normally
closed (NC) port is
disconnected from
the EPO_12V port,
EPO is triggered.
Before delivery, a
short-circuit cable
has been installed
on the NC and 12V
ports.
2 Product Overview
System Action
After the setting
takes effect, the
system will
detect whether
the BCB is
online.
Used to send a
BCB tripping
drive signal.
After the setting
takes effect, the
system will
generate an EPO
alarm and stop
supplying power.
After the setting
takes effect, the
system will
generate an EPO
alarm and stop
supplying power.
41

Advertisement

Table of Contents
loading

Table of Contents