● Cables can be routed in and out from the bottom only when a tail frame is
● The ATS cabinet is used as an example. For details about cable connections for
● Connect the internal cables first, and then the external cables.
Procedure
Step 1 Remove the cover plate from the cable hole at the bottom of the tail frame.
Step 2 Remove the insulation panel from the rear of the cabinet.
Step 3 Connect a ground cable to the UPS cabinet.
Figure 4-32 Connecting a ground cable to the UPS cabinet
Step 4 Connect two AC input power cables to input terminals 1L1, 1L2, 1L3, 1N and 2L1,
2L2, 2L3, 2N respectively in the UPS cabinet.