UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Input voltage range
Input frequency range
Rated frequency
Input power factor
THDi
Overvoltage category
Table 3-6 Bypass input electrical specifications
Item
Input mode
Rated input voltage
Input frequency range
Overvoltage category
Issue 06 (2023-08-25)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
80–280 V AC (phase voltage)
● 30–40°C environment: not derated when the voltage
range is 187–280 V; linearly derated to 40% load
when the voltage range is 187–80 V
● 0–30°C environment: not derated when the voltage
range is 176–280 V; linearly derated to 40% load
when the voltage range is 176–80 V
40–70 Hz
50/60 Hz
> 0.99 (full load); > 0.98 (half load)
≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear
load; maximum: 5%)
OVC II
Specifications
Three-phase four-wire + PE
380/400/415 V AC (line voltage)
50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6
Hz, ±2 Hz by default).
OVC II
3 Technical Specifications