UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
The UPS can generate large leakage currents. A circuit breaker equipped with an
RCD is not recommended.
Table 4-2 Recommended cross-sectional areas for power cables
Item
Input I
Input I current (A)
Recommended circuit
breaker
Recommended
cross-sectional
area (mm
Input II
Input II current (A)
Recommended circuit
breaker
Recommended
cross-sectional
area (mm
Battery
Maximum discharge
(VRLA
current (A)
battery)
Recommended
cross-sectional
area (mm
Battery
Maximum discharge
input
current (A)
(SmartLi)
Recommended cross-
sectional area
Issue 06 (2023-08-25)
NO TICE
UPS5000-
E-125K
(ATS)
385
Three-pole,
400 A
L1
4 x 185
L2
2
)
L3
N
PE
95
385
Three-pole,
400 A
L1
4 x 185
L2
2
)
L3
N
PE
95
328
+
2 x 95
N
2 x 95
2
)
-
2 x 95
PE
95
322
For details, see IEC-60364-5-52 and SmartLi User Manual.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
UPS5000-
UPS5000-
E-125K
E-60K (ATS)
(MCCB)
385
204
Three-pole,
Three-pole,
400 A
250 A
4 x 185
4 x 95
95
50
N/A
184
N/A
Three-pole,
250 A
N/A
4 x 95
50
328
158
2 x 95
95
2 x 95
95
2 x 95
95
95
50
322
155
UPS5000-
E-60K
(MCCB)
204
Three-pole,
250 A
4 x 95
50
N/A
N/A
N/A
158
95
95
95
50
155
77