Huawei UPS5000-E User Manual page 162

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Branch
exception
alarm enable
Voltage
harmonic
alarm
threshold (%)
Current
harmonic
alarm
threshold (%)
System
overvoltage
threshold (%)
System
undervoltage
threshold (%)
Issue 06 (2023-08-25)
Description
If this parameter is set to
Enable, the system generates
an alarm when the branch
circuit breaker is closed and
no load is connected. If this
parameter is set to Disable,
the system does not generate
the alarm under any
condition.
When Harmonic alarm
enable is set to Enable and
the mains voltage harmonic
value exceeds the alarm
threshold, the system
generates an alarm.
When Harmonic alarm
enable is set to Enable and
the mains current harmonic
value exceeds the alarm
threshold, the system
generates an alarm.
When the mains voltage is
higher than the rated voltage
multiplied by the overvoltage
threshold, the system
generates an alarm.
When the mains voltage is
lower than the rated voltage
multiplied by the
undervoltage threshold, the
system generates an alarm.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 LCD Interface
Default Value
Value Range
Disable
Disable,
Enable,
Custom
30.0
5.0–30.0
30.0
5.0–30.0
120.0
105.0–125.0
85.0
75.0–95.0
154