UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Step 8 Set the ATS controller to auto mode.
----End

6.3 Powering On and Starting the UPS

Issue 06 (2023-08-25)
Table 6-3 Device configuration attributes and values
Item
Voltage
Thresholds
Frequency
Thresholds
Modbus
Language Selection
Copyright © Huawei Digital Power Technologies Co., Ltd.
Values
Volt Threshold
–30% to –5%
Min LN1
Volt Threshold
–30% to –5%
Min LN2
Volt Threshold
+5% to +30%
Max LN1
Volt Threshold
+5% to +30%
Max LN2
Freq Threshold
–10% to –1%
Min LN1
Freq Threshold
–10% to –1%
Min LN2
Freq Threshold
+1% to +10%
Max LN1
Freq Threshold
+1% to +10%
Max LN2
– Modbus
– Local/Remote
English; Deutsch;
Francais;
Itatiano; Espanol;
Suomi; Russian;
Chinese
6 Power-On and Commissioning
Description
The step increase
is ±1%. The
default settings
are –10% for
LN1 and LN2.
The step increase
is ±1%. The
default settings
are +10% for
LN1 and LN2.
The step increase
is ±1%. The
default settings
are –5% for LN1
and LN2.
The step increase
is ±1%. The
default settings
are +5% for LN1
and LN2.
There is no need
Address
to reset the
parameter.
Set the
parameter based
on site
requirements.
168