Huawei UPS5000-E User Manual page 182

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Figure 6-2 Standard BSC mode
Step 2 Set the BSC master system. On the LCD of one UPS, choose System Info >
Settings > System Settings and set BSC master/slave mode to BSC master
system.
Figure 6-3 BSC master system
Step 3 Set the BSC slave system. On the LCD of the other UPS, choose System Info >
Settings > System Settings and set BSC master/slave mode to BSC slave
system.
Figure 6-4 BSC slave system
Step 4 If no alarm is generated after settings, the system runs properly.
----End
Issue 06 (2023-08-25)
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On and Commissioning