Huawei UPS5000-E User Manual page 87

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Table 4-4 Power cable terminal requirements
Port
Connection
Description
Mode
AC input
Crimped OT/DT
terminals
Battery input
Crimped OT/DT
terminals
PE
Crimped OT/DT
terminals
Safe grounding
Crimped OT/DT
terminals
Issue 06 (2023-08-25)
NO TE
When selecting, connecting, and routing power cables, follow local safety regulations and
rules.
When the external conditions such as cable layout or ambient temperatures change,
perform verification in accordance with the IEC-60364-5-52 or the local regulations.
The currents listed in the table "Recommended cross-sectional areas for power cables" are
measured at a rated voltage of 380 V; if the rated voltage is 400 V, multiply the currents by
0.95; if the rated voltage is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional areas of the
neutral wires 1.5–1.7 times.
The recommended cables are applicable only when the following requirements are met:
● The cables are routed over a ladder or bracket in a single layer (E or F in IEC
60364-5-523).
● The ambient temperature is 30°C.
● The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
● Single- or multi-core 90°C soft power cables with copper conductors are used.
● It is recommended that AC power cables be no longer than 30 m and DC power cables
be no longer than 40 m.
Bolt
Specifications
M12
M10
M12
M6
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Bolt Hole
Bolt
Diameter
Length
13.5 mm
45 mm
Rivet threaded
30 mm
hole diameter
Rivet threaded
45 mm
hole diameter
Rivet threaded
16 mm
hole diameter
Torque
46 N·m
26 N·m
46 N·m
4.5 N·m
79