6.10 Downloading Data

Procedure
Step 1 Connect a USB storage device to the USB port on the MDU.
Step 2 On the LCD home screen, choose System Info and tap
Maintenance screen.
Step 3 Choose USB Operations > Fault Data, specify the download path, and download
the data.
----End

6.11 Performing EPO

● After the EPO button is turned on, the UPS supplies no power and the loads
● In maintenance bypass mode, the UPS continues to supply power even after
Press the external EPO switch that connects to the dry contact card or remove the
4-pin terminal on the EPO port of the dry contact card of the bypass unit.
Figure 6-14 EPO ports
After you press the EPO button, the EPO and No power supplied alarms are
displayed on the LCD.
Issue 06 (2023-08-25)
NO TE
The capacity test automatically stops in any of the following cases:
● The minimum cell voltage reaches 2.65 V.
● The load fluctuation exceeds 10%.
● An alarm is generated.
The test is complete when the minimum cell voltage reaches 2.65 V. A maximum of recent
36 capacity test records can be saved.
NO TICE
shut down.
the EPO button is turned on.