9.2 Replacing an Indicator

Prerequisites
Tools and Materials
Procedure
Step 1 Remove the indicator fuse from the fuse terminal block at the rear of the cabinet
to disconnect the circuit. For the MCCB input, the fuse is connected to #1 fuse
base. For the ATS input, the fuses are connected to #1 and #2 fuse bases.
Step 2 Remove the protective panel.
Figure 9-3 Removing the protective panel
Issue 06 (2023-08-25)
An indicator is faulty.
A spare indicator of the same model is available and functional.
Phillips insulated torque screwdriver
Key
Protective gloves
Multimeter
Step ladder
Spare indicator
NO TE
A cabinet with ATS input is used as an example.