Figure 56 shows the winding resistance advanced settings.
Figure 56: Winding resistance advanced settings
The stability condition is a reference for the device to decide if the resistance value during a
measurement is considered stable or not. For example, 0.1%/5s means that if the resistance
fluctuations keep less than 0.1% of the average value continuously for more than 5 seconds, it
will be considered stable
When continuous mode is "On Request", one can activate the continuous mode only by
tapping on the continuous button. When mode is "Always", the continuous mode is always
activated automatically.
The maximum acceptable deviation value. Please see chapter 4.2.3 for more information
Preliminary
90297-0.24 Instruction Manual mini-ATOS
Page 73 of 125