8.19

PWM Output Function

The PWM output function outputs the PWM waveform (up to 200kHz) from one of the coincidence output 1 to 4
terminals (EQU1 to EQU4). Up to four points can be assigned for one channel. The same waveform is to be output to
the assigned terminals. The ON width setting (PWM output) can be changed during PWM output.
CH
PWM output assignment setting
CH
ON width setting (PWM output)
(RWw1E to RWw1F, RWw36 to RWw37)
CH
Cycle setting (PWM output)
(RWw20 to RWw21, RWw38 to RWw39)
Remote output signal
CH
PWM output start command
CH
ON width setting change request
(PWM output) (RY35, RY4D)
(1) Restrictions
During operation in the synchronous communication mode, the PWM output function cannot be used. Set "CH
Operation mode setting" to "0: Normal Mode".
(2) Setting method of the PWM output function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window  Select a high-speed counter module in "List of stations". 
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
2.
Set "CH Operation mode setting" to "4: PWM Output Mode".
174
Remote register
(RWw1D, RWw35)
(RY26, RY3E)
High-speed
counter module
Pulse output
PWM output
function
PWM cycle: 5 s to 1s
EQU1 to
EQU4 terminal