Count Disable Function

The count disable function stops the counting when CH Function input terminal (FUNC1, FUNC2) or CH Selected
counter function start command (RY25, RY3D) is input during the counting.
(1) Setting method of the count disable function
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window  Select a high-speed counter module in "List of stations". 
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
2.
Select "0: Count Disable Function" in "CH Counter function selection".
(2) Operation example of the count disable function
The following figure shows an operation example of stopping the counting while CH Selected counter function
start command (RY25, RY3D) and CH Function input terminal (FUNC1, FUNC2) are on.
Controlled by the high-speed counter module
CH
Count enable command
(RY24, RY3C)
CH
Selected counter function
start command
(RY25, RY3D)
CH
Counter function detection
(RX25, RX3D)
CH
Function input terminal
(FUNC1, FUNC2)
CH
Present value
(RWr10 to RWr11,
RWr28 to RWr29)
ON
1)
OFF
ON
2)
3)
OFF
ON
OFF
4)
OFF
0
Count
Count
stop
stop
6)
7)
ON
5)
Pulses actually input
Count value stored in CH
(RWr10 to RWr11, RWr28 to RWr29)
Count
stop
Count stop
CHAPTER 8 FUNCTIONS
8)
9)
Present value
143
8