Mitsubishi Electric NZ2GFCF-D62PD2 User Manual page 181

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

No.
The following processing is performed when CH PWM output start command (RY26, RY3E) is turned on to turn on CH PWM
output (RX26, RX3E).
• The values in CH PWM output assignment setting (RWw1D, RWw35), CH ON width setting (PWM output) (RWw1E to
1)
RWw1F, RWw36 to RWw37), and CH Cycle setting (PWM output) (RWw20 to RWw21, RWw38 to RWw39) are acquired.
• The PWM waveform is output from one of the coincidence output 1 to 4 terminals (EQU1 to EQU4) based on the settings. (The
PWM waveform is output starting with OFF.)
The PWM waveform continues to be output based on the acquired settings until CH PWM output start command (RY26, RY3E)
2)
is turned off or CH ON width setting change request (PWM output) (RY35, RY4D) is turned on.
When the values in CH PWM output assignment setting (RWw1D, RWw35), CH ON width setting (PWM output) (RWw1E to
RWw1F, RWw36 to RWw37), and CH Cycle setting (PWM output) (RWw20 to RWw21, RWw38 to RWw39) are changed, the
3)
PWM waveform is not changed. Only the value in CH ON width setting (PWM output) (RWw1E to RWw1F, RWw36 to RWw37)
can be changed by CH ON width setting change request (PWM output) (RY35, RY4D).
The following processing is performed when CH ON width setting change request (PWM output) (RY35, RY4D) is turned off
then on to turn on CH ON width setting change completed (PWM output) (RX35, RX4D).
• The value in CH ON width setting (PWM output) (RWw1E to RWw1F, RWw36 to RWw37) is acquired.
• The PWM waveform is output from one of the coincidence output 1 to 4 terminals (EQU1 to EQU4) based on the settings. The
4)
change is reflected immediately.
Turn off CH ON width setting change request (PWM output) (RY35, RY4D) when CH ON width setting change completed
(PWM output) (RX35, RX4D) turns on. CH ON width setting change completed (PWM output) (RX35, RX4D) turns off when
CH ON width setting change request (PWM output) (RY35, RY4D) is turned off.
The following processing is performed when CH PWM output start command (RY26, RY3E) is turned off to turn off CH PWM
5)
output (RX26, RX3E).
• Turn off the coincidence output 1 to 4 terminals (EQU1 to EQU4) immediately.