(6) Module-based parameter data (address: 0106
Address
Name
CH1
CH2
Coincidence output
0106
enable command
H
setting
(7) Module-based parameter data (address: 0120
Address
Name
CH1
CH2
Operation mode
0120
0140
H
H
setting
Count source
0121
0141
H
H
selection
• Set this area to determine the coincidence output enable command to be
used for the coincidence output function.
• The following shows the setting range.
0: By each channel
1: By each coincidence output
• To use CH Coincidence output enable command (RY20, RY38), set By
each channel (0).
• To use Enable command (Coincidence output 1 to 4) (RY18 to RY1B), set By
each coincidence output (1).
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned on
• Set the operation mode for channels.
• The following shows the setting range.
0: Normal Mode
1: Frequency Measurement Mode
2: Rotation Speed Measurement Mode
3: Pulse Measurement Mode
4: PWM Output Mode
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
• Set the count source.
• The following shows the setting range.
0: A Phase/B Phase
1: Coincidence Output 1
2: Coincidence Output 2
• When CH Count source selection (address: 0121
Coincidence Output 1 (1) or Coincidence Output 2 (2), pulses are counted
up at the rising edge of the following signals.
Normal mode: Coincidence output 1 to 2 (RX10 to RX11)
PWM output mode: Coincidence output 1 to 2 terminals (EQU1 to EQU2)
• The reflection timing of the setting value
When Initial data setting request flag (RY9) is turned off then on
)
H
Description
to 0121
, 0140
H
H
Description
, 0141
) is set to
H
H
APPENDICES
Default
0
to 0141
)
H
H
Default
0
0
291