Mitsubishi Electric NZ2GFCF-D62PD2 User Manual page 286

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(11)Remote registers (RWw16 to RWw17, RWw2E to RWw2F)
Address
(RWw)
Item
CH1
CH2
Time unit setting
(Sampling
16
2E
counter/Periodic
pulse counter)
Cycle setting
(Sampling
17
2F
counter/Periodic
pulse counter)
284
• Set a unit of time for the sampling counter function or the periodic pulse counter
function.
• The following shows the setting range.
0: 1ms
1: 10ms
• The reflection timing of the setting value
1)
When Initial data processing request flag (RX8) turns off
2)
When Initial data setting request flag (RY9) is turned off then on (only while
Initial data processing request flag (RX8) is off)
3)
When CH Setting change request (Sampling counter/Periodic pulse
counter) (RY27, RY3F) is turned off then on
• Set the sampling period for the sampling counter function or the cycle time of
the periodic pulse counter function.
• The following shows the setting range.
1 to 65535 (When CH Time unit setting (Sampling counter/Periodic pulse
counter) (RWw16, RWw2E) is set to 1ms (0), the sampling period or the cycle time
is indicated in increments of 1ms and when set to 10ms (1), in increments of
10ms.)
• The reflection timing of the setting value
1)
When Initial data processing request flag (RX8) turns off
2)
When Initial data setting request flag (RY9) is turned off then on (only while
Initial data processing request flag (RX8) is off)
3)
When CH Setting change request (Sampling counter/Periodic pulse
counter) (RY27, RY3F) is turned off then on
Description
Default
0
0