8.2

Drive Mode Switch

The drive modes of the high-speed counter module are the normal mode (asynchronous communication mode) and
synchronous communication mode.
The following table lists the type and the operation of the mode.
Type
Normal mode (asynchronous
communication mode)
Synchronous communication mode
The drive mode can be selected by setting Mode switch setting (address: 0000
(1) Setting procedure
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window  Select a high-speed counter module in "List of stations". 
[CC IE Field Configuration]  [Online]  [Parameter Processing of Slave Station]
2.
Set "Mode switch setting" to "0: Normal mode (Asynchronous communication mode)", or "9:
Automatical judgment mode".
The following table lists the setting value of "Mode switch setting" and the drive mode.
Setting value of "Mode switch
setting"
0: Normal mode (Asynchronous
communication mode)
"9: Automatical judgment mode"
*1
The drive mode varies depending on the module of the master station as shown below.
Master station
Master/local module (not support the CC-Link IE
Field Network synchronous communication
function)
Master/local module (supports the CC-Link IE
Field Network synchronous communication
function)
Serial number (first five
digits) is 15091 or earlier
Simple motion
module
Serial number (first five
digits) is 15092 or later
*2
For the settings of the master station, refer to the MELSEC iQ-R Inter-Module Synchronization Function Reference
Manual.
102
The present value is updated with reference to the internal control cycle of the high-speed counter
module.
The present value is updated in the synchronization cycle of a master station that supports the CC-
Link IE Field Network synchronous communication function.
The high-speed counter module operates in the normal mode (asynchronous communication
mode).
The drive mode is automatically set according to the type of the module that operates as the
master station of the high-speed counter module.
Setting of master station
Setting the network synchronous
communication setting to
"Asynchronous"
Setting the network synchronous
communication setting to
"Synchronous"
Operation
).
H
Operation
*1
Drive mode when "Mode switch
*2
setting" is set to "9: Automatical
judgment mode"
Normal mode (asynchronous communication
mode)
Normal mode (asynchronous communication
mode)
Synchronous communication mode
Normal mode (asynchronous communication
mode)
Synchronous communication mode