System Specifications; Batteries; System Grounding; Dc Output - Mitsubishi Electric UBC75 Installation, Operation & Maintenance Manual

Battery cabinet
Table of Contents

Advertisement

6. S
S
YSTEM
PECIFICATIONS
6.1 B
ATTERIES
Please refer to system drawings for model specific information.
Type: Valve Regulated Lead Acid (VRLA), sealed, non-spillable
Voltage: 12 VDC Nominal
Only cabinets with Flame Retardant Batteries are suitable for computer room
use.
6.2 S
G
YSTEM
ROUNDING
All system ground wires should be derived from the main building ground source.
Cabinet Safety Ground: Each cabinet is supplied with a mechanical ground lug that accepts bare
wire from #6 AWG to 300 MCM cable.
Torque: 325 lb-in
Wire Size and Type: Ground wire should be sized per NEC and/or all applicable national and
local codes.
Battery Cabinet Breaker or Fuse Size
Up to 200 amps
201-300 amps
301-400 amps
401-500 amps
501-600 amps
6.3 DC O
UTPUT
Please refer to system drawings for model specific information.
Voltage: 12-480 VDC Nominal
Circuit Breaker: UL Listed 600 VDC rated. See system drawings for details.
Fuse Type:
Gould Type 4 A50P (for 384VDC Nominal bus or less)
Gould Type 4 A70P (for 480VDC Nominal bus or less)
Gould Type HSJ
Wire Size and Type: Per NEC and/or all applicable national and local codes.
Wire should be sized for a maximum voltage drop of 0.5 volt.
6.4 G
S
ENERAL
PECIFICATIONS
Cabinet Size: 48.5"W x 33.5"D x 84"H
Empty Cabinet Weight (approximately): 1000 lbs.
5/30/2014
UBC75 B
Minimum Copper Ground Wire Size
6 AWG
4 AWG
3 AWG
2 AWG
1 AWG
12
C
ATTERY
ABINET
755-00052-M R01

Advertisement

Table of Contents
loading

Table of Contents