Mitsubishi Electric NZ2GFCF-D62PD2 User Manual page 282

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

(6) Remote registers (RWr21 to RWr23, RWr39 to RWr3B)
Address
(RWr)
Item
CH1
CH2
21
39
External input status
22
3A
Latest error code
23
3B
Latest warning code
280
• This area stores the input statuses of phase Z, the function, the latch counter,
phase A, and phase B of the external I/O connector.
b15
b14
b13
b12
b11
b10
b9
0
0
0
0
0
0
0
0 (fixed)
• When CH Operation mode setting (address: 0120
Frequency Measurement Mode (1), Rotation Speed Measurement Mode (2), or
PWM Output Mode (4), Function input status (RWr21.b1, RWr39.b1) is always
OFF (0).
• With Negative Logic (1) being set in CH Function input logic setting (address:
0127
, 0147
) or CH Latch counter input logic setting (address: 0128
H
H
0148
), its input status changes to OFF (0) when a voltage is applied.
H
• When Initial data setting request flag (RY9) is turned off then on, the value in this
area is cleared.
• This area stores the latest error code of the generated major error or moderate
error.
• When multiple errors in the same category occur, this area stores the error code
of the later error.
• When a moderate error occurs while a major error is occurring, this area does
not store the error code of the moderate error.
• For the error code, refer to Page 225, Section 11.2.
• This area stores the error code of the generated minor error.
• When multiple minor errors occur, this area stores the error code of the later
error.
• For the error code, refer to Page 225, Section 11.2.
Description
b8
b7
b6
b5
b4
b3
b2
b1
0
0
0
0
, 0140
H
Default
b0
Phase Z input
status
0: OFF
1: ON
Function input
status
0: OFF
1: ON
Latch counter
input status
0: OFF
1: ON
Phase A input
status
0000
H
0: OFF
1: ON
Phase B input
status
0: OFF
1: ON
) is set to either of
H
,
H
0000
H
0000
H

Advertisement

Table of Contents
loading

Table of Contents