Mitsubishi Electric NZ2GFCF-D62PD2 User Manual page 26

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

No.
Name
Station number setting
1)
switch
PW LED (green)
RUN LED (green)
MODE LED (green)
D LINK LED (green)
2)
ERR. LED (red)
CH1A/B/Z LED
CH2A/B/Z LED (green)
CH1FNC/LAT LED
CH2FNC/LAT LED (green)
EQU1 to EQU4 LED (green)
P1
3)
P2
Terminal block for module
4)
power supply and FG
5)
DIN rail hook
Connectors for external
6)
devices (40 pins)
24
A rotary switch for the following setting and test
• Station Number Setting ( Page 57, Section 6.1)
• Unit Test ( Page 246, Section 11.4)
When operating the station number setting switch, use a slotted screwdriver with 3.5mm or less width
of the tip.
Indicates the power supply status of the module.
• ON: Power supply ON
• OFF: Power supply OFF
Indicates the operating status of the module.
• ON: Operating normally
• OFF: When a major error occurs
Indicates the mode status of the module.
• ON: In online mode
• Flashing: In unit test mode
• OFF: At the unit test completion
Indicates the data communication status between the module and the master module.
• ON: Data link in operation (cyclic transmission in progress)
• Flashing: Data link in operation (cyclic transmission stopped)
• OFF: Data link not performed (disconnected)
Indicates the error status of the module.
• ON: A moderate error or major error has occurred.
• Flashing: A minor error (warning) has occurred.
• OFF: Operating normally
Indicates the input status of the pulse input terminals in phase A, B, and Z.
• ON: At voltage application
• OFF: At no voltage application
Indicates the input status of the function/latch counter input terminal.
• ON: At voltage application
• OFF: At no voltage application
Indicates the output status of the coincidence output 1 to 4 terminals (EQU1 to EQU4).
• ON: Signal output ON
• OFF: Signal output OFF
PORT1 connector for CC-Link IE Field Network (RJ45 connector)
Connect an Ethernet cable. ( Page 67, Section 6.5)
There are no restrictions on the connection order of the cables for the P1
connector and P2 connector.
• ON: The module has received abnormal data or the module is performing
loopback.
L ER LED (red)
• OFF: The module has received normal data or the module is not performing
loopback.
ON: Linkup in progress
LINK LED (green)
OFF: Linkdown in progress
PORT2 connector for CC-Link IE Field Network (RJ45 connector)
Connect an Ethernet cable. ( Page 67, Section 6.5)
There are no restrictions on the connection order of the cables for the P1
connector and P2 connector.
L ER LED (red)
(Same as the P1)
LINK LED (green)
A terminal block to connect the module power supply (24VDC) and FG.
A hook to mount a module on a DIN rail
Connectors for encoders, controllers, and others
(For the terminal layouts, refer to  Page 73, Section 6.6.3)