Mitsubishi Electric NZ2GFCF-D62PD2 User Manual page 238

Cc-link ie field network high-speed counter module
Table of Contents

Advertisement

Error code
Classification
(hexadecimal)
671
Moderate error
H
672
Moderate error
H
673
Moderate error
H
810
Moderate error
H
236
Description and
Error name
cause
A value other than 0
and 10 to 10000000 is
set in CH ON width
CH ON width
setting (PWM output)
setting error (PWM
(RWw1E to RWw1F,
output)
RWw36 to RWw37).
 indicates the
channel where
settings are incorrect.
A value other than 50
to 10000000 is set in
CH Cycle setting
(PWM output)
CH Cycle setting
(RWw20 to RWw21
error (PWM output)
RWw38 to RWw39).
 indicates the
channel where
settings are incorrect.
The value in CH
Cycle setting (PWM
output) (RWw20 to
RWw21, RWw38 to
RWw39) is smaller
CH ON
than the value in CH
width/Cycle setting
ON width setting
error (PWM output)
(PWM output)
(RWw1E to RWw1F,
RWw36 to RWw37).
 indicates the
channel where
settings are incorrect.
A value other than 0 to
4 is set in CH
Operation mode
setting (address:
CH Operation
0120
, 0140
mode setting error
H
 indicates the
channel where
settings are incorrect.
Operation of when an error
occurs
Error CH
If CH PWM
output start
command
(RY26, RY3E)
is turned off
*12
then on:
*3
If CH ON
width setting
change request
(PWM output)
(RY35, RY4D)
is turned off
*1
then on:
*12
*3
,
If CH PWM
output start
command
(RY26, RY3E)
is turned off
*12
then on:
*3
If CH ON
width setting
change request
(PWM output)
(RY35, RY4D)
is turned off
*1
then on:
*13
).
H
Action
The other
CHs
Set CH ON width setting
(PWM output) (RWw1E to
RWw1F, RWw36 to RWw37) to
0 or a value between 10 and
10000000, and perform either
of the following operations.
• If CH PWM output (RX26,
RX3E) is off, turn off then on
 PWM output start
command (RY26, RY3E).
• If CH PWM output (RX26,
RX3E) is on, turn off then on
CH ON width setting
change request (PWM
output) (RY35, RY4D).
Set CH Cycle setting (PWM
output) (RWw20 to RWw21,
RWw38 to RWw39) to a value
between 50 and 10000000, and
turn off then on CH PWM
output start command (RY26,
RY3E).
Set the values that satisfy the
condition "CH ON width
setting (PWM output) (RWw1E
to RWw1F, RWw36 to RWw37)
 CH Cycle setting (PWM
output) (RWw20 to RWw21,
RWw38 to RWw39)", and
perform either of the following
operations.
• If CH PWM output (RX26,
RX3E) is off, turn off then on
CH PWM output start
command (RY26, RY3E).
• If CH PWM output (RX26,
RX3E) is on, turn off then on
CH ON width setting
change request (PWM
output) (RY35, RY4D).
Set CH Operation mode
setting (address: 0120
to a value between 0 and 4, and
turn off then on Initial data
setting request flag (RY9).
, 0140
)
H
H

Advertisement

Table of Contents
loading