3.3

Calculating Current Consumption

The total current consumption of the modules is calculated by summing the module power supply current in the main
module and extension module.
The power supply current in the extension module must be within 30mA.
For the value of the module power supply current, refer to the specifications of each module.
• Performance specifications of the high-speed counter module ( Page 29, Section 3.2)
• Performance specifications of extension I/O module ( CC-Link IE Field Network Remote I/O Module
User's Manual)
The value of the module power supply current in the extension module described in the specifications is the value of
the module power supply current supplied from the main module.
High-speed counter module
NZ2GFCF-D62PD2
Module power supply current: 220mA
34
Extension module
NZ2EX2B1-16T
+
Module power supply current: 30mA
250mA
=
(Total current consumption)