Installation

2.7 IPOTS-COM Communicator

Two independent telephone lines can be connected to the control panel via the IPOTS-COM Optional Phone/IP Communication Module.
Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is
critical that the IPOTS-COM Digital Communicator be located as the first device on the incoming telephone circuit to properly function.
Important! The IPOTS-COM must not be used to dial a phone number that is call-forwarded.
Network
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point

Wiring

Connection and wiring of two phone lines is required as shown below.

Dip Switches

There are two configurable dip switches on the IPOTS-COM communicator.
SW3: 2-position DIP switch- Factory Settings- Do not change unless instructed to do so
by Honeywell.
SW2: 6-position DIP switch- FUTURE USE- No configuration necessary.

Remote Connection Feature

For compliance with ULC-S527, the ribbon cable at J1 (refer to Figure 2.10 for location) must
be disconnected when testing the FACP. This will prevent communication with the central
station and trigger a trouble at the panel. When testing is complete, reconnect the ribbon cable
and cycle power on the panel. This will clear the trouble.
28
RJ31X
Jack
FACP with IPOTS-COM
mounted internally
Telephone
Answering
System
Figure 2.11 Communicator Installation
IPOTS-COM
J3
J4
J5
LINE1
LINE2
ETH
Module Female
Connectors
Male Plug
Connectors
Figure 2.12 Wiring Phone Jacks
Customer Premises Equipment and Wiring
Unused
RJ-11 Jack
Fax Machine
(Secondary Lines)
Incoming Telco Phone Lines
green
Ring
Tip
To premise phones
red
Ring
Tip
1 2 3 4 5 6
7
8
RJ31X
Jack
Note: Shorting
bars inside RJ31X
Jack removed
during installation.
Secondary
7 foot Cable
Phone Line
MCBL-7
(ordered
separately)
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
IPOTS-COM Communicator
Computer
Telephone
Unused
RJ-11 Jack
Telephone
Tip green
(Primary Lines)
red
Incoming Telco Phone Lines
Ring
Ring
To premise phones
Tip
1 2 3 4 5 6 7
8
RJ31X
Jack
Primary Phone Line
SW3
SW2
Figure 2.13
IPOTS-COM DIP
Switches

Hide quick links: