3=Program Check; 4: Walktest - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Maintenance Programming Level
Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY, PLEASE WAIT to be displayed. The display
will then return to the History Screen. Pressing 2 will cause the display to return to the History Screen without erasing the History file.
3.6.3 Program Check
PROGRAMMING
1=POINT PROGRAM
2=HISTORY

3=PROGRAM CHECK

Maintenance Screen #1
The Program Check feature allows the programmer to view the zones which have been programmed to the Notification Appliance Circuits
on the control panel but have not been programmed to Initiating Devices as well as other circuits with no input or output correlations. Press-
ing 1 while viewing Program Check screen will cause a screen similar to the following to be displayed.
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but no input devices have been programmed
to any of these zones. Use the up and down arrow keys to view all the NAC zones without input assignments for both NAC 1, NAC 2, NAC
3 and NAC 4.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device (not
including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to
an addressable module (control module in this example) with an address of 001 on loop 1 but have not been programmed to any input
devices. Use the up and down arrow keys to view all the zones without input assignments.
Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be displayed:
The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not
including general alarm Zone 00). The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to
an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and down arrow
keys to view all the zones without output assignments.
3.6.4 Walktest
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest. Pressing 1 or 2 will cause the control panel to enter
Walktest Mode and will display the following screen:
From this screen, it is possible to view the walktest log, untested system points or a summary of the addressable devices tested during the
current walktest. The user can select between any of these screens without interrupting the current walktest session. The walktest session will
not end until the Unit In Walktest screen is exited by pressing the Escape key to return to the Walktest Screen.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
NACS NO INPUT
NAC 1
025 031 044 055 067
ZONES NO INPUT
005 007 009 010 011
1M001
ZONES NO INPUT
005 007 009 010 011
1M001
To perform a walktest, press 1 while viewing Maintenance Screen #2. The following screen will be displayed:
1=SILENT
2=AUDIBLE
3=VIEW RESULT
UNIT IN WALKTEST
1=VIEW WALKTEST LOG
2=VIEW POINTS
3=VIEW SUMMARY
Unit In Walktest Screen
PROGRAM CHECK
WALKTEST
Walktest Screen
Programming
99