Digital Alarm Communicator/Transmitter; Components; Optional Modules And Accessories - Honeywell Fire-Lite Alarms MS-5UD Series Manual

Fire alarm control panels
Table of Contents

Advertisement

Digital Alarm Communicator/Transmitter

1.4 Digital Alarm Communicator/Transmitter
Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the fol-
lowing functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact ID
SIA-DCS-8
SIA-DCS-20

1.5 Components

Main Circuit Board
The main circuit board contains the system's CPU, DACT and other primary components and wir-
ing interface connectors. Optional modules plug in and are mounted to the main circuit board.
Power Supply
One power supply is provided standard with each FACP, mounted to a chassis.
FLPS-3 for the MS-5UD-3(E), MS-10UD-3(E)
FLPS-7 for the MS-5UD-7(C/E), MS-10UD-7(C/E)
Cabinet
The backbox measures 16.65" (42.29 cm) x 19.0" (48.26 cm) x 5.207" (13.23 cm) and provides
space for two batteries (up to 18 Amp Hours). Also available are an optional dress panel (DP-
51050) which mounts inside the cabinet and trim-ring (TR-CE). The Canadian version is supplied
standard with a modified dress panel and one ANN-LED annunciator module.
Batteries
The cabinet provides space for two 18 Amp Hour batteries (larger batteries require use of a UL
listed battery box such as the BB-26 or BB-55). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-5X Class A Converter Module
The CAC-5X Module can be used to convert the Style B (Class B) Initiating Device Circuits to
Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J2 on the MS-5UD and MS-10UD main circuit board and to J7 on the MS-
10UD. Note that two Class A Converter modules are required for the 10 zone panel.
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm condi-
tion exists. The 4XTMF mounts to the main circuit board connectors J4 & J5.
MS-5UD & MS-10UD Series Manual — P/N 52626:C2 1/24/2012
Product Description
®
, programmable to rotary
21

Advertisement

Table of Contents
loading

Table of Contents