Zones Available; 4: Loop Setup; Loop; Device Addressing - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level

Zones Available

ZONE SETUP
1=ZONES AVAILABLE
Zone Setup Screen #3
The display will show all of the zones that are still available for programming. Note that an up and/or down arrow may appear in the upper
right corner of the display, indicating that additional screens of zone information exists. Press the up or down arrow key to view additional
screens.
3.5.4 Loop Setup
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=NOT USED
Programming Screen #2

Loop

Select the desired loop for setup by selecting 1 for Loop 1, 2 for Loop 2, or 3 for Loop 3. Loops 2 and 3 are only available if any optional
SLC-3LS Loop Expander cards have been installed. Select the desired loop by pressing the corresponding number. For each loop, the user
can set the SLC-3LS as an installed module, and set wiring class and polling protocol.
Installed
LOOP SETUP
1=INSTALLED
2=CLASS
3=PROTOCOL LITESPEED
Programming Screen #2
Class
To program the SLC Class for the selected loop, press 2 for Class, while viewing Loop Setup Screen. In the preceding example, the FACP is
programmed for Class B SLC wiring as indicated by the B to the right of Class in the display. To change the wiring class, press 1 to toggle
the display to read Class A. Each press of the 1 key will cause the display to toggle between Class B and Class A.
NOTE: If the FACP reports an open fault on an SLC Loop programmed for Class A, the trouble condition will latch at the FACP. When the SLC
Loop has been repaired, the Reset button must be pressed at the FACP (at least 2 minutes after the trouble has been repaired) to clear the SLC
trouble.
Loop Protocol
Loop Protocol refers to the SLC loop mode of operation. Refer to "Wire Requirements" on page 141 for wire specifications based upon SLC
protocol. There are two Loop Protocols available:
CLIP (Classic Loop Interface Protocol) - which is used for the older legacy addressable devices such as the M300 Series modules and
detectors.
LiteSpeed (factory default setting) - used for the 350 Series or newer addressable devices for quicker response times. Note that the
legacy devices can operate only in CLIP mode while the newer devices are compatible with CLIP and LiteSpeed modes of operation.
Pressing 2 while viewing the Loop Setup Screen will toggle between CLIP and LiteSpeed Protocols.

Device Addressing

It is important to note that the FACP addressable device capacity is 159 detectors and 159 control/ monitor modules per SLC loop. Since
older legacy addressable devices cannot be set to addresses above 099, the newer series devices must be used when addresses 100 to 159 are
to be installed. It is permissible to mix old and new devices in the same panel, however, the FACP must be programmed for CLIP mode.
3.5.5 System Setup
System Setup allows the programmer to configure the following control panel features:
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:
Loop Setup allows the programmer to configure the SLC Loop for NFPA Class B or Class A wiring and to
select the loop protocol. Pressing 1 while viewing Programming Screen #2 will cause the following screen to
be displayed:
1=LOOP 1
2=LOOP 2
3=LOOP 3
Loop Setup Screen #1
1=INSTALLED
2=CLASS
3=PROTOCOL LITESPEED
Loop Setup Screen #2
If additional SLC-3LS cards have been installed, adding a second or third SLC loop to the panel, it must be
NO
activated in user programming. After pressing 2 or 3 on Loop Setup Screen #1 for the desired loop, pressing 1
B
while viewing the Loop Setup Screen #2 will cause the display to change to Installed Yes. Each press of the 1
key will cause the display to toggle between Installed Yes and Installed No. Note that Loop 1 is fixed and can-
not be set to Installed No.
ZONES AVAILABLE
001 002 003 004 005
006 007 008 009 010
011 012 013 014 015
LOOP SETUP
LOOP SETUP
YES
B
Programming
67

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-1000xcFire-lite alarms es-1000xi

Table of Contents