Master Programming Level
Ethernet Fault
IP SETTINGS
1=ETHERNET FAULT
MAC CRC
IP Settings Screen #2
Select the number of minutes allowed, 1-60, before a fault is shown on the panel.

Primary and Secondary Communication Paths

COMMUNICATOR
1=PRI COMM PATH
2=SEC COMM PATH
3=TBL CALL LIMIT
Communicator Screen #1
POTS
XXX COMM PATH
1=POTS
2=ETHERNET
Comm Path Screen #1
POTS XXX COMM PATH
1=ENABLED
2=ACCT CODE
000000
POTS (XXX) Path Screen #1
Enable
POTS XXX COMM PATH
1=ENABLED
2=ACCT CODE
000000
POTS Comm Path Screen #1
NOTE: For UL applications: when POTS is used as the primary communication path, the use of POTS as the secondary transmission path is
only allowed with approval of the local AHJ.
For ULC applications: when POTS is used as the primary transmission path, alarm signals will be sent out on both the primary and secondary
transmission paths.
Account Code
Pressing 3 while viewing POTS (XXX) Path Screen #1 will cause the following screen to be displayed:
The Account Code, which is assigned by a Central Station, depends on the communication format being used. The Account Code screen will
have a flashing cursor in the lower left corner. Enter the supplied account code using 0 - 9 and A- F keys.
Phone Number
POTS XXX COMM PATH
1=PHONE NUMBER
POTS Comm Path Screen #2
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
The Ethernet Fault Time is the duration of the communication loss between the FACP and the ethernet infra-
01
structure.
C3F0
Pressing 1 on the IP Settings Screen #2 will display the following:
The Primary and Secondary Communication Path screens are used to configure the methods (primary and
backup) for reporting to central station. Pressing 1 for Pri or 2 for Sec will display the following screens.
Note that the following information must be entered for both the Primary and Secondary Communication Paths.
0
To configure the communication method to contact central station as a telephone line, select 1 for POTS. The
following screens will display.
POTS XXX COMM PATH
NO
1=PHONE NUMBER
POTS (XXX) Path Screen #2
To enable the phone line, press 1 while viewing the POTS Line (X) Screen #1 to change the display to
NO
Enabled Yes. Each press of the 1 key will cause the display to toggle between Enabled Yes and Enabled No.
Pressing 2 while viewing POTS XXX Path Screen #2 will cause the following screen to be displayed:
ETHERNET FAULT TIME
RANGE 1-60 MINUTES
Ethernet Fault Time Screen
XXX COMM PATH
1=POTS
2=ETHERNET
XXX Comm Path Screen
POTS XXX COMM PATH
1=COMM FORMAT
ADEMCO CONTACT ID
POTS (XXX) Path Screen #3
ACCOUNT CODE
ENTER 6 DIGITS
Account Codes Screen
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Numbers Screen
Programming
POTS XXX COMM PATH
1=TEST TIME INT
24
2=24HR TEST TIME
0100
POTS (XXX) Path Screen #4
81