Installation
Specifications
Max. ANN-BUS Voltage: 24 VDC
Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Must be installed adjacent to the main FACP operator interface to meet UL 2017 standards
For indoor use in a dry location only
ANN-I/O Connection to FACP
The ANN-I/O connects to the FACP via the ANN-BUS as illustrated in Figure 2.21. After the ANN-I/O is connected to the panel, it must be
added to the system via FACP programming. Refer to the section titled "ANN-I/O Options" on page 88.
ANN-I/O Module LED Wiring
There are four 12-pin connectors on the ANN-I/O module for connecting LEDs. Each set of 10 LEDs get their power from Pin 11 of the cor-
responding connector. Internal resistors are sized so that there is approximately 10 mA of current for each LED. No series resistors are
required. LED outputs can be mapped to output circuits. Refer to the programming section titled "ANN-I/O Options" on page 88 of this
manual.
The LEDs are wired as illustrated in Figure 2.22. Note that the illustration depicts only connectors P1 and P2. Wiring is identical for P3
(LEDs 21-30) and P4 (LEDs 31-40).
38
10
1
20 21
20
11
LED Out
LED Out
LED Power
LED Power
Not Used
Not Used
ANN-I/O Module
Primary ANN-BUS
24 VDC non-resettable
Figure 2.21 ANN-I/O Connection to FACP
30
31
40
LED Out
LED Out
LED Power
LED Power
Not Used
Not Used
ANN-BUS and DC power wiring are
supervised and power-limited
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023