Read Status; 1=System Point - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Operating Instructions
If the MMF-302 monitor module is used for a supervised, 2-wire smoke zone, alarming any monitor module in the system will result in
the activation of programmed control outputs for an additional eight seconds or less. This is caused by the temporary removal of 24
VDC resettable power from the MMF-302. The MMF-302 reports this loss of power as an open condition in addition to the alarm
condition.
Open Condition
Addressable devices are monitored for fault conditions during Walktest mode. When a new trouble condition occurs, the FACP will activate
all NACs and control modules programmed for Walktest and mapped to the faulty device, then shut them off after eight seconds.
While in Walktest, the trouble relay is activated and the system Trouble LED flashes (as in all of the Program and status change operations).
The alarm relay is not activated.

4.23 Read Status

Read Status functions do not require a password. The control panel will continue to provide fire protection while in Read Status mode. This
mode can be entered while the control panel is in alarm or trouble. If a new alarm or trouble occurs during these functions, the Read Status is
exited to prevent confusion.
Read Status Entry
When the operator presses the control panel
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Status mode which allows the user to view and
print the programmed features and status of the control panel.
The following screens will be displayed:

1=SYSTEM POINT

2=ZONES
3=NOT USED
1=ANNUNCIATORS
2=COMMUNICATOR
3=NOT USED
4.23.1 System Point
READ STATUS
1=SYSTEM POINT
2=ZONES
3=NOT USED
Read Status Screen #1
Then, select the point type. Select 1 for Detector or 2 for Module.
The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for Module. If 1 is pressed, the display will
change to the following screen:
110
ENTER
READ STATUS
Read Status Screen #1
READ STATUS
Read Status Screen #4
Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed. Choose the
loop on which the point is located.
key, the LCD will display the following:
MAIN MENU
1=READ STATUS MODE
2=LOGIN
READ STATUS
1=TROUBLE REMINDER
2=TIMERS
3=NACS
Read Status Screen #2
READ STATUS
1=REVISIONS
2=PRINT
3=TIME/DATE
Read Status Screen #5
READ POINT, LOOP:
1=LOOP 1
2=LOOP 2
3=LOOP 3
READ SYSTEM POINT
SELECT TYPE
1=DETECTOR
2=MODULE
READ SYSTEM POINT
ENTER DETECTOR#
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
READ STATUS
1=RELAYS
2=PROGRAM CHECK
3=HISTORY
Read Status Screen #3
READ STATUS
CHARGER ENAB
YES
4XTM SPV ENAB
NO
REM SYNC ENAB
YES
Read Status Screen #6
Read Status