Section 6: Fs-Tools Upload/Download; Fs-Tools Up/Download - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Important! The FACP will automatically reset 2 minutes after completion of a user program download via the FS-Tools programming util-
ity. To prevent program corruption, the operator must wait until this panel reset occurs before performing any panel operations.
The control panel may be programmed or interrogated off-site via the public switched telephone network or locally using a USB cable. Any
personal computer with Windows
Tools, may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest
data, current status, system voltages, time and date.
The control panel may also communicate to a local PC at the job-site. The PC must be connected to the USB connector J20 on the FACP
main circuit board. A standard USB cable with male-A to male-A connectors, which must be purchased separately, is required.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "FS-Tools
Upload/Download" on page 119). Remote interrogation of panel programming, history logs, detector status, etc., is possible without
enabling the remote download option.
CAUTION: After successfully downloading a program, make certain to perform the following steps:
1.
Print out all programmed data via Print Mode or manually view programmed entries and compare to intended program data
2.
Test all affected panel operations
3.
Immediately correct any problems found

6.1 FS-Tools Up/Download

NFPA 72 requirements state that a technician be on-site and at the control panel whenever the FS-Tools Programming Utility is used to
download any information to the FACP. This applies to local and remote programming.The Remote Download option can be selected from
the main menu screen as shown below after successful login:
Select 2 to login to the panel.
Select 2 to login as a User.
Select the appropriate User login ID:
Enter the User's Master level password. Only a user with master level programming rights can access FS-Tools Up/Downloads. The follow-
ing screen will appear:
Select 2 for FS-Tools Up/Download.
Pressing 1 for Accept Upload will cause the following screen to be displayed:
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023

Section 6: FS-Tools Upload/Download

®
7 or NEWER 32 or 64 bit, with a 2400 baud compatible modem and Upload/Download software FS-
1=READ STATUS MODE
2=LOGIN
SELECT ACCOUNT
1=ADMINISTRATORS
2=USERS
3=NOT USED
1=USER 1
2=USER 2
3=USER 3
LOGIN FOR USER X
ENTER PASSWORD
MASTER MENU
1=PROGRAMMING MODE
2=FS-TOOL UP/DWNLOAD
3=USB UP/DOWNLOAD
FS-TOOL UP/DOWNLOAD
1=ACCECPT UPLOAD
2=ACCEPT DOWNLOAD
ALLOWING UPLOADS
IF YOU EXIT THIS
SCREEN UPLOADS
WILL BE DISABLED!
MAIN MENU
SELECT USER