Basic Operation
5.
Enter the number of seconds you want the notification appliance circuits to sound. From 6 to 180 seconds.
6.
Press <Enter> to end the Walk Test. The system will reset. The panel will send a "TEST RESTORE" Report to the Central Station.
If you do not manually end the Walk Test within four hours, it will end automatically. If an alarm or pre-alarm condition occurs in the
system, you will not be able to enter the Walk Test.
The panel does not do a full 30 second reset on resettable power outputs. As soon as the device returns to normal, the panel is ready to go
to the next device.
8.4.6 Conduct a Communicator Test
1.
From the Main Menu, press 1 for System Tests.
2.
Select 5 for Communicator Test. The screen will display "Manual communicator test started". When the test is completed, you will
be returned to the <Test Menu>. A manual Communicator Test requires that at least one daily test in the network be enabled in
Communicator Programming.
If both Phone Lines and Ethernet/Cellular paths are programmed, the manual Communicator Test will be communicated from both
Phone Lines and Ethernet/Cellular paths. Each manual Communicator Test will alternate between one of the Phone Line paths and one
of the AlarmNet paths.
8.4.7 Manual AlarmNet Registration
1.
From the Main Menu, press 1 for System Tests.
2.
Select 8 for Register AlarmNet. The screen displays and asks confirmation. Feedback will be given if the command was sent or not.
8.4.8 Silence Alarms or Troubles
1.
Press <SILENCE> and enter your code or rotate the key at the prompt.
2.
If you installed an External Silence switch, and you activate the switch, it will silence alarms or troubles.
3.
If you are already using System Menus, when you press <SILENCE>, you do not need to enter your code or rotate the key.
NOTE: Alarm and trouble signals that have been silenced but the detector remains un-restored will un-silence every 4 or 24 hours
depending on the user selection (see Section , "Auto-Resound (4 or 24 hours)") until it is restored.
8.4.9 Reset Alarms
Press <RESET> and enter your code or rotate the key at the prompt. If you installed an External Reset switch, when you activate the
switch, it will reset the alarms. If you are already using System Menus, when you press <RESET>, you do not need to enter your code
or rotate the key.
Reset Communicator
This options allows the user to Reset the Communicator. The LCD will display:
"Communicator Reset in progress... Please Wait"
When the Reset is complete, the Main Menu appears. You cannot reset the Communicator when alarms or supervisories are active. Com-
municator reset is not allowed if any of the following conditions are active:
Fire Alarm
8.4.10 Check Detector Sensitivity Through Point Status
The control panel constantly monitors smoke detectors to ensure that sensitivity levels are in compliance with NFPA Standard 72.
If sensitivity for a detector does not comply with NFPA 72, the panel goes into trouble, generating a CAL TRBLE condition. A detector
enters a CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance).
When a CAL TRBLE condition occurs, the Central Station receives a Detector Trouble Report ("373" and the zone or point for Contact
ID format; "FT" and the zone or point in SIA format).
To check THE sensitivity for an individual detector, follow the steps below:
1.
From the Main Menu, press 2 for Point Functions.
2.
Press 2 for Point Status.
3.
Select the module where the point you want to check is located.
4.
Enter the number of the point you want to check and press <ENTER>.
5.
A screen similar to those shown in Figure 8.3 will display.
You can print detector status by uploading the detector status to and printing from HFSS Honeywell Fire Software Suite.
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
Fire Supervisory
Fire Pre-Alarm
CO Alarm
System Operation
CO Supervisory
63