Controls And Indicators; Digital Alarm Communicator/Transmitter - Honeywell GF505 Manual

Fire alarm control panels
Table of Contents

Advertisement

Product Description

1.3 Controls and Indicators

LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display.
The display includes a long life LED backlight that remains illuminated. If AC power is lost
and the system is not in alarm, the LED backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and
LED indicators as listed above. The key panel, which is visible with the cabinet door closed,
has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
Function keys:
Acknowledge/Step
Alarm Silence
Drill
System Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
1st Event key
Clear key
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
LED Indicators
LEDs are provided to annunciate the following conditions:
Fire Alarm - red LED
Supervisory - yellow LED
AC Power - green LED
System Trouble - yellow LED
Alarm Silence - yellow LED
Primary Phone Line Active (on circuit board) - red LED
Secondary Phone Line Active (on circuit board) - red LED
Kiss-off (on circuit board) - green LED
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance, process monitor and supervisory conditions as
follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse 1 second on and 1 second off
Supervisory - pulse ½ second on and ½ second off
Process Monitor - pulse ¼ second on and ¼ second off

1.4 Digital Alarm Communicator/Transmitter

Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for
Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communi-
cator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s)
varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
 Ademco Contact ID
 SIA-DCS-8
 SIA-DCS-20
16
Figure 1.2 Membrane/Display Panel
®
, programmable to rotary
GF505 & GF510 Manual — P/N 53164:B5 6/12/2018
Controls and Indicators