Maintenance Programming Level - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Maintenance Programming Level

Pressing 2 while viewing the Program Check Screen #1 will display a screen similar to the following:
The Zone No Input screen allows the programmer to view the zones which have not been programmed to at least one input device (not
including general alarm Zone 00). The example in the preceding screen indicates that Zones 005, 007, 009, 010, and 011 have been pro-
grammed to an addressable module (control module in this example) with an address of 001 on loop 1 but have not been programmed to any
input devices. Use the up and down arrow keys to view all the zones without input assignments.
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
The Zone No Output feature allows the programmer to view the zones which have not been programmed to at least one output device (not
including general alarm Zone 000). The example in the preceding screen indicates that Zones 005, 007, 009, 010, and 011 have been pro-
grammed to an addressable detector with an address of 001 on loop 1 but have not been programmed to any output devices. Use the up and
down arrow keys to view all the zones without output assignments.
3.6 Maintenance Programming Level
To enter the maintenance programming level, an Administrative user must have enabled the User in password setup and granted the User
access to programming at the Maintenance level. To access user programming mode at the maintenance level, press the Enter key. The LCD
will display the following.
Select 2 to login to the panel.
Select 2 to login as a User.
Select the appropriate User login ID:
Enter the User's Maintenance level password. The following screen will appear:
Note that in the preceding screens, an arrow appears to inform the programmer that additional options can be viewed by pressing the keypad
down arrow key, as shown in the following screen.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
ZONES NO INPUT
005 007 009 010 011
1M001
Pressing 3 while viewing Program Check Screen #1 will cause a screen similar to the following to be dis-
played:
005 007 009 010 011
1D001
1=READ STATUS MODE
2=LOGIN
1=ADMINISTRATORS
2=USERS
3=NOT USED
1=USER 1
2=USER 2
3=USER 3
LOGIN FOR USER X
ENTER PASSWORD
MAINTENANCE MENU
1=POINT PROGRAM
2=HISTORY
3=PROGRAM CHECK
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
ZONES NO OUTPUT
SELECT ACCOUNT
SELECT USER
PROGRAMMING
1=PASSWORD CHANGE
Programming
97