Installation

2.7 IPOTS-COM Communicator

Two independent telephone lines can be connected to the control panel via the IPOTS-COM Phone/IP Communication Module. Tele-
phone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note that it is
critical that the IPOTS-COM Digital Communicator be located as the first device on the incoming telephone circuit to properly function.
Important! The IPOTS-COM must not be used to dial a phone number that is call-forwarded.
Network
Service
Provider's
Facilities
Telephone
Line
Network
Demarcation
Point

Wiring

Connection and wiring of two phone lines is required as shown below.
30
RJ31X
Jack
FACP with IPOTS-COM
mounted internally
Telephone
Answering
System
Figure 2.11 Communicator Installation
IPOTS-COM
J3
J4
J5
LINE1
LINE2
ETH
Module Female
Connectors
Male Plug
Connectors
Figure 2.12 Wiring Phone Jacks
Customer Premises Equipment and Wiring
Unused
RJ-11 Jack
Fax Machine
Telephone
(Secondary Lines)
Incoming Telco Phone
Tip Green Wire
Ring
To premise phones
Red Wire
Ring
Tip
1 2 3 4 5 6
7
8
RJ31X
Jack
Note: Shorting
bars inside RJ31X
Jack removed
during installation.
Secondary
7 foot Cable
Phone Line
MCBL-7
(ordered
separately)
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
IPOTS-COM Communicator
Computer
Telephone
Unused
RJ-11 Jack
Ti Green
(Primary Lines)
Incoming Telco Phone
Red Wire
Rin
Ring
To premise
Tip
1 2 3 4 5 6 7
8
RJ31X
Jack
Primary Phone Line

Advertisement

Table of Contents
loading