Programming

Invalid Password

If a password is entered incorrectly or is not a valid password, the panel will display either of the following messages.
The programmer may hit the Escape or Enter key and re-enter the password correctly.

Incorrect Password/Timeout

A user has nine attempts to enter the correct password. If the password is incorrect after the nine attempts, the administrator must wait 30
seconds for another attempt. However, if the password has been forgotten, it will need to be reset by the administrator.
3.5.10 Clear Program
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
Pressing 1, for Whole System while viewing the Clear Program Screen, will clear all general system programming options and all pro-
grammed addressable devices from the nonvolatile memory of the FACP. This function is useful when the control panel is first installed,
prior to autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System function.
Pressing 2, for All Points while viewing the Clear Program Screen, will clear all programming related to the SLC loop and connected
addressable devices.
Pressing 3, for Loop1 will clear all devices on this SLC loop.
Pressing 1 on Clear Program Screen #2, will clear all devices on SLC loop2. Pressing 2 on Clear Program Screen #2 will clear all devices on
SLC loop3.
Before executing any of the Clear commands listed above, the control panel will provide a warning to the user by prompting with the follow-
ing display:
Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will prevent programming from being cleared.
3.5.11 Program Check
PROGRAMMING
1=PASSWORD CHANGE
2=CLEAR PROGRAM
3=PROGRAM CHECK
Programming Screen #4
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
The example above indicates that NAC 1 has been programmed to Zones 025, 031, 044, 055 and 067 but no input devices have been pro-
grammed to any of these zones. Use the up and down arrow keys to view all the NAC zones without input assignments for NAC 1, NAC2,
NAC 3 and NAC 4.
96
MODIFY USER X
USER X PASSWORD
IS INCORRECT
PRESS ENTER OR ESC
INVALID PASSWORD
PRESS ENTER OR ESC
Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will cause the
LCD to display the following screen:
CLEAR PROGRAM
1=WHOLE SYSTEM
2=ALL POINTS
3=LOOP1
Clear Program Screen #1
SYSTEM CHANGE!
1=YES
The Program Check feature allows the programmer to view the zones which have been programmed to the
Notification Appliance Circuits on the control panel but have not been programmed to Initiating Devices as
well as other circuits with no input or output correlations. Pressing 3 while viewing Programming Screen #4
will cause the following screen to be displayed:
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen #1
Pressing 1 while viewing the Program Check Screen will display an NAC screen similar to the following.
NACS NO INPUT
NAC 1
025 031 044 055 067
MODIFY USER X
NEW PASSWORD CANNOT
BE ALL THE SAME CHAR
PRESS ENTER OR ESC
00 ATTEMPTS
REMAINING
CLEAR PROGRAM
1=LOOP2
2=LOOP3
Clear Program Screen #2
WARNING!
PROCEED?
2=NO
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023