Relays; Canadian Option - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming

Relays

SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
To program Relay 1 or Relay 3, press the number corresponding to the selected relay. Note that Relay 2 is fixed as a Trouble relay. Selecting
Relay 2 will have no effect on its programming. The following screen will appear for each programmable relay:
Pressing 1 for Type while viewing the Relay Screen will cause the following screens to be displayed:
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
While viewing the selected screen, press the number corresponding to the desired relay type to program the main circuit board relay. The
choice will be stored in memory and the display will return to the Relay Type Screen which will show the programmed type choice. Press the
Escape key to return to the Relays Selection Screen and repeat the preceding procedure for the remaining relays.
NOTE:
1. AR (AutoResettable) in SUPERVISORY AR and PROCMON AR means that a relay with the Supervisory and/or Process Monitor type code,
when activated, will automatically reset when the corresponding condition is cleared.
2. A relay programmed with the Silenceable Alarm type will activate upon any alarm and deactivate when the FACP Alarm Silenced LED is
illuminated.

Canadian Option

Pressing 1 while viewing System Setup Screen #3 will configure the FACP to comply with Canadian requirements. The display will change
to Canadian Opt. On. Each press of the 1 key will cause the display to toggle between Canadian Opt. On and Canadian Opt. Off.:
Important! For Canadian Applications, this option must be set to ON prior to any other panel programming.
The Canadian Options configures the FACP with the following as required by Canada:
The following monitor module type codes are not available:
monitor
non-latching drill
non-latching process monitor
process monitor
hazard
tornado
medical alert
The following features become available:
Sounder Base Auto Silence
Control Module Auto Silence
Special Zone 251 CO Active
Special Zone 250 In Suite Silence
Control Module Auto Silence Timer
In Suite Silence Timer
In Suite Resound Timer
Programmable NAC Silence Inhibit
ANN-Bus annunciator keys enable
Control modules are no longer associated with the auto silence setting for NAC 1.
76
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to configure two main circuit
board Form-C relays from the following screen:
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
1=TYPE
Relay Type Screen
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS MON
Relay Screen #2
1=CANADIAN OPT.
2=WATERFLOW SIL.
3=MNS OVERRIDE
RELAYS
RELAY #
ALARM
RELAY
1=PROCESS MON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
SYSTEM SETUP
OFF
NO
NO
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
RELAY
1=MEDICAL
2=SILENCEABLE ALARM
3=CARBON MONOXIDE
Relay Screen #4