Calculating The Battery Size; 1: Nfpa Battery Requirements; 2: Selecting And Locating Batteries - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Calculating the Battery Size

3
Refer to the Device Compatibility Document for standby current.
4
Must use compatible listed Power Supervision Relay.
5
Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
6
When powered by an external source, use 0.040A. When powered by the SLC, use 0.024A.
7
If using Gentex brand NACs, the max number of devices for each NAC output is 35. The "UL Max" current rating, published in their data sheets, must be used
in order to maintain performance under low battery conditions with the maximum wire resistances shown in Table D.2 on page 142.
8
Total Alarm current load cannot exceed 9.4 amps.
9
When AC power is initially applied to the panel and the battery is not fully charged, an initial charge current of up to 3.1 amps may be observed at the battery.
This high current is only applied for a very short duration (milliseconds) and does not affect system load or battery size calculations.
10 Total Standby current load cannot exceed 3.9 amps.
9.4 Calculating the Battery Size
Use Table 9.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH),
required to support the system upon loss of primary (AC) power. Complete Table 9.4 as follows:
1.
Enter the totals from Table 9.3 on page 126, Calculation Columns 2 and 3 where shown
2.
Enter the NFPA Standby and Alarm times (refer to 'NFPA Requirements' below)
3.
Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours
4.
Multiply the sum by the derating factor of 1.25 to calculate the proper battery size (in AH)
5.
Write the ampere hour requirements on the Protected Premises label located inside the cabinet door
Total Standby Load, Battery Powered
(from Table 9.3 Calculation Column 3)
[
Total Fire Alarm Load, Battery Powered
(from Table 9.3 Calculation Column 2)
[
Sum of Standby and Alarm Ampere Hours
Multiply by the Derating Factor
Battery Size, Total Ampere Hours Required
9.4.1 NFPA Battery Requirements
NFPA 72 Local, Proprietary, Central, Auxiliary and Remote Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in
alarm
9.4.2 Selecting and Locating Batteries
Select sealed lead acid batteries that meet or exceed the total ampere hours calculated in Table 9.4 . The control panel can charge batteries in
the 18 AH to 55 AH range. The control panel cabinet is capable of housing batteries up to 26 AH. Batteries larger than 26 AH require a UL
listed external battery charger and cabinet such as the BB-26, BB-55F, or other UL listed external battery cabinet.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Required Standby Time
(24 hours)
]
X[
Required Alarm Time
(for 5 min., enter 0.084,
]
for 10 min., enter 0.168)
X[
Table 9.4 Total Secondary Power Requirements at 24 VDC
]
=
]
=
=
X 1.25
=
Power Supply Calculations
AH
AH
AH
AH
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms es-1000xcFire-lite alarms es-1000xi

Table of Contents