Master Programming Level
Delete Detector
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as
005. When the last digit is keyed-in, the following screen will be displayed:
The programmer can continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen.
Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen. The following screen
will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such as
017.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device that
is installed with a lower address, closest to the selected address, will be displayed.
If no detectors have been installed on the loop, the following will be displayed:
If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer to
view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices at the
previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication fault
but the address is programmed in the system, the following screen will be displayed:
If the selected address has been added to programming and a detector (such as a photoelectric detector) with the selected address is physi-
cally installed on the SLC and is communicating with the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keypad 'down' arrow key to view the Edit Detector screens.
In the preceding example:
Normal - indicates that the detector with the selected address is physically installed on the SLC and communicating with the control
panel (enabled)
<ADJ><NOUN> - represents the adjective and noun, which have been programmed, describing the location of the displayed device
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to
delete a specific detector:
DELETE DETECTOR
ENTER DETECTOR#
Delete Detector Screen
DELETE DETECTOR
DETECTOR#
IS DELETED
EDIT DETECTOR
ENTER POINT ADDRESS
Edit Detector Screen
Edit Detector Screen #1
TROUBL SMOKE(PHOTO)
<ADJ><NOUN>
Edit Detector Screen #1
NORMAL SMOKE (PHOTO)
<ADJ><NOUN>
Edit Detector Screen #1
005
NO DETECTOR
INSTALLED
ZNNN
1D017
ZNNN
V
1D017
Programming