Programming
Silenceable
Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This will prevent the selected main circuit
board NAC from being silenced by pressing the Alarm Silence key or by the Auto Silence feature. Each press of the 3 key will cause the dis-
play to toggle between Silenceable Yes and Silenceable No.
Important: When a Notification Appliance Circuit with a mix of audible and visual devices is programmed for silenceable and the Synced
Strobe feature is selected, only the audible devices will be turned off if the Silence key is pressed or if the Auto Silence feature is enabled. The
visual devices (strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or Auto Silence will turn off both
audible and visual devices.
Auto Silence
NAC #
1=AUTO SILENCE
2=CODING
STEADY
NAC Screen #2
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To enable the Auto Silence feature, press the num-
ber corresponding to the time delay which will elapse before Auto Silence activates. This information will be stored in memory and the dis-
play will return to NAC Screen #2.
NOTE: All silenceable control modules as well as the remote power supply sync will be controlled by the Auto Silence timer for NAC 1.
Coding (only for NACs not programmed as Sync Strobe Type)
The Coding feature allows the programmer to select the type of output that the main circuit board notification appliances will generate when
activated. Pressing 2 while viewing NAC Screen #2 will cause the following displays to appear:
1=STEADY
2=MARCH TIME
3=CALIFORNIA
The programmer can select the notification appliance output by pressing the number corresponding to the desired output. The coding selec-
tions are:
Steady - a continuous output with no coding
March Time - 120 ppm (pulse-per-minute) output
California - 10 seconds on and 5 seconds off
Temporal 3 - ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, 1½ Seconds Off
Temporal 4 - ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, ½ Second Off, ½ Second On, 1½ Seconds Off
Two Stage - refer to, "Two Stage Operation" below for a description
Selection of one of the above options will cause the control panel to store the information in memory and return the display to NAC Screen
#2, which will display the new coding choice.
Two Stage Operation
Two Stage operation consists of the following:
1st stage output - 20 ppm (pulse-per-minute) coding
2nd stage output - Temporal coding as described above
F2 button functions as the automatic alarm signal cancel button
F3 button functions as the two stage advance to second stage button
NOTE: Two-stage operation cannot be used at the same time as in-suite silence feature.
If Two Stage operation is programmed as the Coding option, the following sequence of events will occur during an alarm.
1.
The onboard NACs which are programmed to General Alarm Zone 000 will activate with a 1st stage output upon activation of any
alarm point.
2.
If the activated alarm point is directly mapped to a zone which is programmed to an onboard NAC, that NAC will go directly to 2nd
stage coding output. All other NACs not directly mapped to the activated alarm point's zone but assigned to Zone 0 will activate with a
1st stage output.
3.
If, after the programmed time of 3 or 5 minutes, the Acknowledge switch has not been pressed, all NACs presently in 1st stage
activation will go to 2nd stage activation.
74
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable notification
appliances after a programmed length of time. To enable this feature and program the time delay before Auto
Silence activation, press 1 while viewing NAC Screen #2. The following screens will be displayed:
AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen #1
CODING
1=TEMPORAL 3
2=TEMPORAL 3
3=TWO STAGE 3 MIN
Coding Screen #1
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
CODING
1=TWO STAGE 5 MIN
Coding Screen #2
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Master Programming Level
AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #3
CODING
Coding Screen #3