Banner; Time/Date - Honeywell Fire-Lite Alarms ES-1000X Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Master Programming Level
NACs
Each function key can be assigned to control any of the 4 onboard NAC circuits on the ES-1000X. By pressing the 2 key while viewing the
Function Keys Screen #2 the following screen displays, allowing the user to select the desired NAC circuit(s).
Pressing 1, 2, 3, or 4 toggles the screen between Yes (controlled by function key) and No (not controlled by function key) for each onboard
NAC circuit.
Remote Sync Disable
F(X) OPERATION
1=NACS
1,2,3,4
2=REM SYNC DISB
Function Keys Screen #2

Banner

SYSTEM SETUP
1=FUNCTION KEYS
2=BANNER

3=TIME/DATE

System Setup Screen #1
Pressing 1 while viewing the Banner Screen will select the blank factory default banner setting and display the following screen:
Pressing the Enter key will store this selection in nonvolatile memory and return the display to the Banner Screen.
Pressing 2 while viewing the Banner Screen will cause the following screens to be displayed:
These screens allow the programmer to enter a two line custom banner. A flashing cursor will appear in the bottom left corner of each dis-
play. A maximum of 20 characters (including spaces) can be entered into each screen for a total of two lines with 40 characters. After enter-
ing up to 20 characters in the first screen, press Enter to view the second screen. Enter up to 20 characters in the second screen in the same
manner or just press Enter if a second banner line is not being entered. To quickly clear the current banner, press the CLR key.
To enter alphanumeric characters from the keypad, repeatedly press the appropriate key until the desired character is displayed in the first
position. For example, to enter the letter B, press the 2 (ABC) key three times to toggle through the characters 1, A, and B. Press the right
arrow key to move the cursor one position to the right and repeat the process to enter the next character. To enter a space, press the * (QZ)
key four times to place a blank in the desired position. When all characters have been entered, press the Enter key to store the information.
The display will return to the Banner Screen.
Time/Date
SYSTEM SETUP
1=TROUBLE REM
2=BANNER
3=TIME/DATE
System Setup Screen #1
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
1=NAC 1
2=NAC 2 Y
The Remote Synchronization (TB8 on the FACP's main circuit board) can also be disabled through program-
ming of a function key.To disable remote synchronization, press the 3 key while viewing the Function Keys
NO
Screen #2. Each press of the key will toggle the screen between Rem Sync Disb Yes and Rem Sync Disb No.
The top line of the display, which appears when the control panel is in normal mode, can be changed by using
the Banner option. Pressing 2 while viewing System Setup Screen #1 will cause the following to be displayed:
USER BANNER - LINE 1
ENTER OR PRESS ENTER
User Defined Banner Screen #1
The control panel time and date can be changed by pressing 3 while viewing the System Setup Screen #1. The
following screen will be displayed:
TIME AND DATE
1=TIME
2=DATE
3=CLOCK FORMAT
Time-Date Screen #1
F(X) NACS
Y
3=NAC 3
4=NAC 4
Function Keys Screen
BANNER
1=FACTORY
2=USER DEFINED
Banner Screen
FACTORY BANNER
Factory Banner Screen
USER BANNER - LINE 2
ENTER OR PRESS ENTER
User Defined Banner Screen #2
1=DAYLIGHT SAVING
06:34 AM
12-18-2022
12HR
N
N
TIME AND DATE
Time-Date Screen #2
Programming
69