Controls and Indicators
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED
backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED
backlight will turn off to conserve batteries.
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and
LED indicators as listed below. The key panel, which is visible with the cabinet door closed, has 30 keys, including a 16 key alpha-numeric
pad similar to a telephone keypad.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•
Fire Alarm (red)
•
CO Alarm (yellow)
•
AC Power (green)
•
Supervisory (yellow)
•
Trouble (yellow)
•
Ground fault (yellow)
•
Battery fault (yellow)
•
Disabled (yellow)
•
Maintenance (yellow)
•
Communication (yellow)
•
Alarm Silenced (yellow)
•
F1-F4 Function keys (yellow)
Function keys:
•
Acknowledge
•
Alarm Silence
•
Drill
•
Reset (lamp test)
•
four (4) programmable function keys
Service/program keys:
•
Keys labeled 1 to 9
•
* key
•
# key
•
0 key
•
First Event and scroll keys
•
Last Event and scroll keys
•
Clear key
•
Escape key
•
Two cursor keys (left and right)
•
Menu/Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
1.4 Components
Main Circuit Board
The main circuit board contains the system's CPU, power supply, other primary components and wiring interface connectors. The 4XTMF
option module plugs in and is mounted to the main circuit board.
SLC Loop Card
The ES-1000X ships with one loop card mounted to the main circuit board. A maximum of 318 devices can be connected to the SLC loop in
Class A, Class B, or Class X configuration.
ES-1000X Series Manual — P/N LS10133-000FL-E:A 6/21/2023
Product Description
SYSTEM NORMAL
10:00A 121822
Figure 1.2 Membrane/Display Panel
15