7.3.5
Wiring the 110...240 V AC electrical supply for a
8619 multiCELL WM AC
Fig. 15:
Wiring the 110...240 V AC electrical supply for a 8619 multiCELL WM AC
48
M0
M1
M2
M3
M4
M5
M6
110-240 V~
50/60 Hz
L
N
PE
N
PE
L
English
→ Unscrew and remove the
Protective cover
→ Use the rightmost cable
Removable screw
terminals, 2-positions,
green
→ Wire the 110...240 V AC
PE
L N
→ Connect the protective
L: Live conductor
N: Neutral conductor
→ Put in place and screw on
Type 8619
Installation and wiring
protective cover of the
power supply connection
terminal block.
gland for the electrical
power supply cable.
power supply for a
8619 multiCELL WM AC
on a terminal block marked
110...240 V AC.
earth of the installation
to the earth screw of the
device (see section 5,
Fig. 3) using a lug with
an eyelet, suitable for the
M4 earth screw and earth
conductor. Tighten with
a torque of 1 Nm ±20 %
(0.74 lbf·ft ±20 %).
the protective cover.