Type 8619
Installation and wiring
7.3.4
Wiring the 12...36 V DC electrical supply for a
8619 multiCELL WM DC
→ Use a filtered and regulated 12...36 V DC electrical power supply.
→ Use the rightmost cable gland for the electrical power supply cable.
→ Wire the 12...36 V DC power supply for a 8619 multiCELL WM on a terminal block marked 12...36 V DC.
→ Connect the functional earth of the installation to the earth screw of the device (see section 5, Fig. 2)
using a lug with an eyelet, suitable for the M4 earth screw and earth conductor. Tighten with a torque of
1 Nm ± 20 % (0.74 lbf·ft ± 20 %).
→ Connect the shielding on each wire to an "FE" (functional earth) terminal to guarantee the equipotentiality
of the installation.
Fig. 14:
Wiring the 12...36 V DC electrical supply for a 8619 multiCELL WM
M0
M1
M2
M3
M4
M5
M6
FE
Removable
screw terminals,
2-positions, green
+
-
FE
12-36 VDC
-
+
Electrical power supply
English
47