Configuring A Time Dosing Cycle - Burkert 8619 Operating Instructions Manual

Modular transmitter/controller
Hide thumbs Also See for 8619:
Table of Contents

Advertisement

9.19

Configuring a time dosing cycle

This function is available as an option. See section 9.5.
It is used to add one or two products to the process, either at regular intervals ("DoMode" = "Period"), or
according to the days of the week ("DoMode" = "Week"). The quantity added is proportional to the time
open (programmable) of the command unit.
Real time clock
Process input
(PV)
Fig. 78:
"Time dosing" function
If the message "M0:W:Time lost" is generated, the dosing cycle cannot be carried out. See
section 16.3.5.
Once the function has been configured and activated, the result "Fx:" calculated is available in the
list of process variables on the "M0:MAIN" board. This list appears in the output configuring, user
view configuring and datalogging menus to:
• Assign the result "Fx:" calculated to a physical output (analogue, AO, or digital, DO)
(see sections 9.25 and 9.26).
• Display the result "Fx:" on one of the user defined "Ux" views: see section 9.9.
• Logging the values of "Fx:" using the datalogger: see section 9.22.
120
Channel 1
Channel 2
English
Type 8619
Parameters menu
System switch
Fallback
position 1
Fallback
position 2
Result (Fx: CMD1)
Result (Fx: CMD2)