Installing A 8619 Multicell Wm On A Support - Burkert 8619 Operating Instructions Manual

Modular transmitter/controller
Hide thumbs Also See for 8619:
Table of Contents

Advertisement

Fig. 11:
Panel mounting of the device on an enclosure or cabinet
7.2.2
Installing a 8619 multiCELL WM on a support
NOTICE
Risk of material damage the cable glands are loosened. The body of the cable glands are screwed into
the housing at the factory with a torque of 5.5 Nm (4.06 lbf·ft)
▶ Before installing the wall-mounting housing on its support, check that the bodies of the cable glands are tight-
ened. If the bodies of the cable glands are loose, tighten them with a torque of 5.5 Nm ± 20 % (4.06 lbf·ft ± 20 %).
The 8619 multiCELL WM is installed on a support using the wall-mounting fastening plate.
→ Choose a location such that:
• The surface is plane.
• The surface temperature of the support remains below 100 °C.
• The display is at eye level.
• There is sufficient space to open the housing by 180°.
42
English
Type 8619
Installation and wiring
Step 5:
→ Place the fastener flush against the device by hand,
so that the hooks remain in place.
Step 6:
→ Fully tighten the screws using an appropriate
screwdriver.
→ Repeat steps 4 to 6 to fit the remaining 3 fasteners.