Type 8619
Technical data
6.9
Electrical specifications of the
8619 multiCELL WM AC
Electrical supply 110...240 V AC
• Tolerance
• Frequency
• Max. current
• Integrated protection
Power distribution
(POWER OUT module)
Maximum cur-
rent of the load
[A]
1.3
1.1
0.8
0.6
0.1
0
-20
Fig. 10:
Derating curves of the maximum permissible current, depending on the ambient temperature
All digital inputs ("DI")
• –10...+10 %
• 50...60 Hz
• 550 mA
• delayed 3.15 A fuse, 250 V AC, (breaking capacity = 1500 A at
250 V AC, 10 kA at 125 V AC), certified IEC 60127, UL-listed
and UL-recognized
• Protected against polarity reversal
• 24 V DC, filtered and regulated, device permanently connected
to a Safety Extra-Low Voltage circuit (SELV circuit), at a non-
hazardous energy level,
•
1.3 A max.: observe the maximum permissible load as a
function of the ambient temperature. See the derating curves
Fig. 10.
-10
0
+10 +20 +30 +40 +50 +60 +70
• Switching threshold V
• Switching threshold V
• Input impedance: 3 kΩ
• Galvanically isolated
• Protected against polarity reversal and voltage spikes
• Frequency: 0.5...2500 Hz
+80
[°C]
Ambient temperature
: 5...36 V DC
on
: < 2 V DC
off
8619 multiCELL WM AC,
without extension module
8619 multiCELL WM AC,
with extension module
English
31