Configure The Profinet Controller Module - Emerson PACSystems RX3i Application Manual

Genius dual bus
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Application Guide
GFK-2928C
Figure 23: Assign Ethernet Status Address
Note that there are additional port settings for LAN1 and LAN2. These will require
configuration entries as well.
5.5

Configure the PROFINET Controller Module

The PROFINET Controller Module has a 32-bit diagnostic/status reference. The
recommended starting reference is %I16465 (the next available reference following the
Ethernet port status reference).
Figure 24: Assign PROFINET Status Address
Note:
Figure 25: Disable Port Criticality (for Debug only)
PLC Hardware Configuration
For each slot in which a PROFINET Controller is installed, the Primary module and the
Secondary module will always have identical Status Addresses. (However, the PROFINET
Controllers from one slot to another will have separate, unique addresses).
For the purposes of early project development/debug, it may be simpler to disable the port
criticality parameters. However, these should be enabled before the project is installed in an
operating environment.